  Datasheet File OCR Text:
 Current Transducer HAT 500..1500 - S
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN = 500 .. 1500 A VOUT = 4 V
Preliminary
Electrical data
Primary nominal r.m.s. current IPN (A) 500 800 1000 1200 1500 Primary current measuring range IP (A) 1500 2400 3000 3000 3000 Type
HAT HAT HAT HAT HAT
500-S 800-S 1000-S 1200-S 1500-S
Features
* Hall effect measuring principle * Galvanic isolation between primary * * * *
and secondary circuit Isolation voltage 3000 V Low power consumption Extended measuring range(3 x IPN) Insulated plastic case recognized according to UL 94-V0
VC IC Vd Vb R IS VOUT ROUT RL
Supply voltage ( 5 %) Current consumption R.m.s. voltage for AC isolation test, 50/60Hz, 1mn R.m.s. rated voltage, safe separation Isolation resistance @ 500 VDC Output voltage @ IPN, RL = 10 k, TA = 25C Output internal resistance Load resistance
15 V 15 mA 3 kV 5001) V > 1000 M 4V 40 mV 100 >1 k
Accuracy-Dynamic performance data
Advantages
<1 <1 < 20 % of IPN % of IPN mV
X
L
VOE VOH VOT TCG tr f
Accuracy @ IPN, TA = 25C (without offset) Linearity 2) (0 .. IPN) Electrical offset voltage, TA = 25C Hysteresis offset voltage @ IP = 0; after an excursion of 1 x IPN Thermal drift of VOE Thermal drift of the gain (% of reading) Response time @ 90% of IP Frequency bandwidth (- 3 dB) 3)
* Easy mounting * Small size and space saving * Only one design for wide current * High immunity to external
interference. ratings range
< 10 mV <1 mV/K < 0.1 %/K <5 s DC .. 50 kHz
Applications
* DC motor drives * Switched Mode Power Supplies
General data
TA TS m Ambient operating temperature Ambient storage temperature Mass Standards 4) - 10 .. + 80 - 15 .. + 85 app. 300 EN 50178 C C g
* AC variable speed drives * Uninterruptible Power Supplies * Battery supplied applications * Power supplies for welding
applications (UPS)
(SMPS)
Notes :
Pollution class 2, overvoltage category III. Linearity data exclude the electrical offset. 3) Please refer to derating curves in the technical file to avoid excessive core heating at high frequency. 4) Please consult characterisation report for more technical details and application advice.
1) 2)
991201/4
LEM Components
www.lem.com























▲Up To Search▲   

 
Price & Availability of HAT1000-S

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X